Electroluminescent Exit Sign | White or Black Housing | Energy Efficient
Base Code: LEC-G
UL Listed
This item has been tested and meets safety standards imposed by the Underwriters Laboratories (UL).
Electroluminescent
The most energy efficient lighting source requiring a power supply.
Made in the USA
This unit is made in the United States.
Features
- UL 924, CSA, NEC, OSHA, and NFPA 101 Life Safety Code
- Made in USA
- Electroluminescent powered
- Less than 1/5 watts energy draw
- 120/277 VAC operation
- Universal mounting canopy included
- Knock-out left/right arrows
- Impact and scratch resistant polycarbonate/ABS housing
Previous Product Codes: LEC-W, LEC-B
Specifications
Dimensions (May Vary by Model) | |
Width | 12.88" |
Height | 8.88" |
Depth | .63" |
Weight | 4.00 lb |
What's included?
- LEC Exit Sign
- "EXIT" Faceplate (with optional knockout arrows)
- One Blank Faceplate (Matching faceplate for double sided option)
- Mounting Canopy, Installation Instructions & Hardware
- NiCad Battery - Must connect the battery after installation
Construction
The LEC-G LEC sign is contructed with a two piece high-impact ABS-FR engineering grade thermoplastic housing. Impact-proof, scratch resistant, corrosion-proof, UV-stable, UL94-5VA flame rating, Injection-molded in the USA.
Illumination
Electroluminescent exit signs are powered by electroluminescence using LECs (light emitting capacitors) and “smart” driver technologies. The lamps themselves are less than half the thickness of a credit card contributing to the ultra-thin design of the sign.
Emergency Operation
Upon failure of the normal utility power, an internal solidstate transfer switch automatically provides uninterrupted emergency operation for at least 120 minutes. Recharging a discharged battery happens within 24 hours.
Battery - Battery Backup
The LEC-G Electroluminescent Exit Sign is designed with a maintenance-free NiCad battery that provides a minimum emergency duration of 120 minutes. Recharge time of the battery is 24 hours. Operational temperature range is 65°F (18°C) to 85°F (30°C).
Operational Temperature
Temperature Ratings | |
Series | Temperature |
Standard Option | -40°F to 140°F |
Electrical Components
Dual voltage 120/277 input operation. For battery backup units, a LED display indicates AC/ON. An external push button test switch allows maintenance personnel to quickly determine operational status.
Installation
The LEC-G is suitable for surface wall, side and top mounting via included canopy. Knock-out chevrons for customized egress signage.
Mounting Configurations Explained