Hazardous Location Rated Green LED Exit Sign | Class 1 Division 2
Base Code: LEDC1D2-G
Class I Division 2 Rated
This product has been tested for hazardous and industrial environments.
LED Lighting
This product uses energy efficient and long lasting LED's.
Battery Included
This product contains a battery for backup power. The battery must be connected during installation.
Features
- UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes
- Rated for Class 1, Division 2, Groups A, B, C & D.
- UL Listed for Wet Locations & IP66 Rated for Ingress Protection
- 120/277 VAC dual-voltage input
- Internal solid-state transfer switch
- Universal knockout pattern on back
- Fiberglass reinforced polycarbonate construction
Specifications
Dimensions (May Vary by Model) | |
Height | 9" |
Depth | 2.88" |
Length | 13.13" |
Weight | 20.00 lb |
What's included?
- Green LED C1D2 Rated Exit Sign
- Mounting Hardware
- Installation Instructions
Construction
The LEDC1D2 Exit Sign housing is contructed of fiberglass reinforced polycarbonate in a gray finish. Corrosion-resistant enclosure with one piece design features improved impact resistantance, UV stabilized polycarbonate lens, molded gasket and stainless steel hardware. Tamper-proof hardware is available to prevent unauthorized access to the unit.
Emergency Operation
Upon failure of the normal utility power, an internal solid-state transfer switch automatically provides uninterrupted emergency operation for at least 90 minutes. The fully automatic solid-state, two-rate charger initiates recharging a discharged battery within 24 hours.
Battery - Battery Backup
The LEDC1D2 Exit Sign series incorporates a 4.8V maintenance-free NiCad battery (Battery Backup and Self-Testing Models Only) that provides a minimum emergency duration of 90 minutes. Recharge time of the battery is 24 hours.
Operational Temperature
Temperature Ratings | -20°C to 50°C / -4°F to 122°F |
Self-Testing Option
Self-test models perform an monthly, biannual and annual test to ensure reliable operation and compliance to electrical/life-safety codes.
Electrical Components
120/277 VAC operation. LED display indicates AC/ON. Unit offers surge protected, solid state circuitry. Battery backup models offer an external push button test switch, brownout detection, AC lockout, low voltage disconnect and visual LED system fault indicator.
Installation
The LEDC1D2 Exit Sign series is suitable for wall, ceiling and side mount (Polycarbonate mounting bracket included). Knockouts provided for conduit feed applications.
Mounting Configurations Explained
View Installation Instructions