Wet Location Exterior Green LED Exit Sign

Base Code: WLT-G

Items marked FAST SHIP typically ship same day if order is placed before noon

Wet Location Exterior Green LED Exit Sign
Processing...

Get Help

Lead Time:
Non Standard Options: 7-10 Day

Qty

Exterior exit sign! Ultra bright, compact unit provides the affordability you've been looking for in a high-end package. Long life LEDs and NiCad battery make this unit energy efficient and maintenance free! Standard unit is capable of operating in temperatures 10° to 40 °C / 50 °F to 104 °F.


Compatible Battery:  3.6V 500mAh

Compatible Remote Head(s): RHP-L-3V, RHB-L-MV, RHB-WPL-MV
To use with remote heads, please change the Operation Type above to Battery Backup + Remote Head Capable to ensure compatibility. Code at time of checkout must read: WLT-G-RH.

This product has been tested to meet all required U.S. standards by Underwriters Laboratories, Inc. (UL), the most widely recognized U.S. nationally recognized testing laboratory (NRTL).

UL Listed
This item has been tested and meets safety standards imposed by the Underwriters Laboratories (UL).

LED Lighting

LED Lighting
This product uses energy efficient and long lasting LED's.

Battery Included

Battery Included
This product contains a battery for backup power. The battery must be connected during installation.

Features

  • UL 924, NEC and NFPA 101 Life Safety Code
  • Listed for wet location
  • Ultra bright LEDs
  • Suitable for top, side, and wall mount installations
  • Push-to-test switch
  • 120 or 277 VAC operation
  • Extremely low operating costs
  • Removable directional indicators
  • 5VA Flame retardant, UV stabilized polycarbonate enclosure
  • Maintenance free NiCad battery

Previous Product Codes: WLT-G

Specifications

Dimensions (May Vary by Model)
Width2.5"
Height8.5"
Length12.5"
Weight10.00 lb

What's included?

  • GREEN LED Exit Sign
  • One "EXIT" Faceplate (with optional knockout arrows)
  • Additional matching faceplate (extra cost)
  • One Blank Faceplate
  • Mounting Canopy, Installation Instructions & Hardware
  • NiCad Battery - Must connect the battery after installation

Construction

The WLT-G series is constructed of 5VA flame retardant, UV stabilized polycarbonate housing. High impact, UV stabilized polycarbonate lens included, some discoloration may occur over time if installed in direct sunlight. Fully gasketed with engineering grade silicone. White housing is standard.

Illumination

The WLT-G series uses ultra bright, energy efficient green LEDs.

Emergency Operation

Upon failure of the normal utility power, an internal solidstate transfer switch automatically provides uninterrupted emergency operation for at least 90 minutes. The fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours.

Battery - Battery Backup

The WLT-G series is designed with a maintenance-free NiCad battery that provides a minimum emergency duration of 90 minutes. Recharge time of the battery is 24 hours. The battery is protected by a low voltage cut-off circuit.

Operational Temperature

Temperature Ratings
Series Temperature
Standard Option32°F to 104°F
Expanded Temperature Rating -4°F to 104°F

Self-Testing Option

Unit continuously monitors the AC power, battery supply voltage, emergency lamp condition and charging circuit. If failure is detected, the indicator will show status and correct when adjusted. Unit will automatically perform NFPA required monthly and annual testing. Refer to user manual for details.

Remote Head Capable Option

The remote head capability option allows the WLT unit to supply power to up to two additional LED remote heads. The remote heads would then operate on the same emergency mode as the standard units (see Emergency Operation Section).

Electrical Components

Dual voltage input 120/277 VAC operation. LED display indicates AC/ON. An external push button test switch allows maintenance personnel to quickly determine the operational status of the unit.

Installation

The WLT-G is suitable for side mount and top mount with the included mounting canopy. Universal knockout pattern can be found on the blank faceplate for wall mount installations. Snap together design allows for quick and easy installation. Knock-outs provided for conduit feed applications. Knock-out chevrons for customized egress signage.

Mounting Configurations   Mounting Configurations Explained

PDF Download   View Installation Instructions

Dimensions

Wet Location Exterior Green LED Exit Sign Dimensions

Customer Questions & Answers
Post a question and have an expert answer



Q Thomas ORourke • 10/26/2022, 8:41:38 AM Does your exit sign have wiring for a EM Led head
A Exit Light Co. The WLT-G does come with a remote head capable option. This would allow it to operate one double remote head or two single remote heads. Under the “Operation Type” drop down please select “Remote Head Capable”.
Post a question and have an expert answer